# EnOcean > Symcon documentation · English · generated on 2026-09-26 > Index: https://www.symcon.de/en/llms.txt Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/ EnOcean is a wireless system that is supported by multiple manufacturers. For a connection to IP-Symcon a USB or LAN interface is required. > **Note:** The following devices are supported by IP-Symcon: > > __[Supported Devices (incl. gateways)](enocean.md)__ and __[EEP List](enocean.md) __ ### Installation The __USB Gateway__ is connected to the server and is accessible via Serial Port. The __Symcon LAN Gateway__ is connected to the server via LAN. For the configuration, the IP-Symcon "Network Configuration Tool" is required. It is available for [Download](https://support.symcon.de/lan-gct) . A simple [Description for Configuration of the Gateway (German)](https://www.symcon.de/assets/files/service/NetworkConfigurationTool.pdf) is available. Afterwards, the gateway can be accessed at the corresponding IP address and Port (default: 5000). > **Note:** If no IP-Symcon house is printed on the front of the LAN gateway, it is an older model of the gateway. The installation manual for that model can be downloaded [here (German)](https://www.symcon.de/assets/files/service/EnOceanLAN-Gatewayrev.vor2015.pdf) . The __Eltako FGW14__ is connected to a SymBox with over RS232. The SymBox must have the RS232 module fitted. The FGW14 is in turn connected to the __Eltako FAM14__ via the "Eltako Bus14" pluggable jumper bridges. The following connectivity configuration is to be observed: **FAM14:** - **Rotary Mode Selector (BA):** Set According to manual. Select mode 2 for bi-directional communication. Select mode 1 for address assignment. - **Terminal Pins "N" and "L":** Connect with 230V mains power. Either by attaching a suitable mains plug or connect directly to live and neutral rail inside a control cabinet or fuse box. - **Terminal Pin "Hold":** Connect with terminal pin "Hold" on FGW14. - **Terminal Pin "GND":** Connect with ground pin (⊖) of the RS232 interface of the SymBox. **FGW14:** - **Rotary Mode Selector (BA):** Select mode 6: "Bus14 ↔ RS232 58k Baud". - **Terminal Pin "Hold":** Connect with terminal pin "Hold" on FAM14. - **Terminal Pin "Tx":** Connect with terminal pin ↓ of the RS232 interface of the SymBox. - **Terminal Pin "Tx":** Connect with terminal pin ↑ of the RS232 interface of the SymBox. ### Integration into IP-Symcon When using the LAN gateway it can be integrated via [Device Search](../components/management-console.md). This is realized by selecting the system "EnOcean Discovery". The Discovery instance offers the creation of an EnOcean [Configurator](../concepts.md). After the configurator was created, individual devices can be integrated as described below. The USB gateway is directly created as configurator as it cannot be found via [Device Search](../components/management-console.md). This is done by creating an "EnOcean Configurator" in the [Object Tree](../components/management-console.md). During the configuration of the interface, the according ESP2 or ESP3 mode must be selected and finally the according port selected and opened. > **Note:** How the I/O instance (parent instance of the gateway) is selected and eventually replaced, can be found here: [Replace I/O Instance](../how-to.md) ### Configuration Depending on the device type, the configuration differs. There are four different device types. Each has its one different approach during configuration. (see below in the corresponding section) > **Warning:** To use an EnOcean device, it must be taught in explicitely into IP-Symcon. > **Warning:** Every Device ID (0-127) may only be given once. > **Note:** Before starting a search, the parent instance needs to be configured. The correct serial ports need to be entered and the configuration applied. The setting of Baud rate etc. is not required and is done automatically by the system. A general tutorial for creating devices/instances in IP-Symcon can be found here: [Integrate Devices](../how-to.md) #### Configurator The configurator can create any EnOcean device as instance. This is done by selecting "New device", clicking "Create", and selecting the according device from the list. ![EnOcean Configurator](https://www.symcon.de/media/pages/service/dokumentation/modulreferenz/geraete/enocean/289bba4744-1790424938/enocean-configurator1.png) After the configurator has created the instance and the configuration button was pressed, the configuration for the device instance opens. Here, the Device ID can be searched and selected by pressing the "Search" button and multiple confirmations on the EnOcean device. ![EnOcean Device ID Search](https://www.symcon.de/media/pages/service/dokumentation/modulreferenz/geraete/enocean/2c30e80e71-1790424938/enocean-search-deviceid.png) ![EnOcean Configurator](https://www.symcon.de/media/pages/service/dokumentation/modulreferenz/geraete/enocean/aa83f719cc-1790424938/enocean-configurator2.png) New instances are created in the main category in the Object Tree. These created instances can be renamed and positioned at another location. It is also possible to open the corresponding instance configurations via "Configure" in the configurator. #### Actor - Enter Device ID and confirm with "Apply" - Put device into teach in mode (see manufacturer manual) - Click "Teach In" - Eventually test functionality with On/Off in the test environment | ID | Description | | --------- | ----------------------------------------------------- | | Device ID | Provided by the user. 0-127 in whole numbers possible | #### Actor (Eltako) * Assign an ID to the devices via login at the FAM14 (see manufacturer manual) * Enter Device ID and confirm with "Apply" * It can be seen easiest via the PCT14 * Put device into teach in mode (see manufacturer manual) * Click "Teach In" in the IP-Symcon instance * Eventually test functionality with On/Off in the test environment * Click "Search". The device should switch On/Off five times * Select found ID and confirm with "OK" __Special handling for certain devices__ * __FUD14:__ In PCT14, in the configuration area, the options "Confirmation Telegram with Dim Value" and "Confirmation Telegram with Button Telegram" must be set to "On". If not inserted by the teach in, the function 32 "Dim Value from GFVS / Rotary Switch" must be configured in function group 3 of the tab "ID - Allocation Area" of the device. * __FSR14-xR:__ Must be teached in as directional button or universal button, depending on whether the button should switch On/Off or switch with two buttons. * __FSB14:__ If not inserted by the teach in, the function 32 "Drive Time with predefined time value FVS" must be configured in the function group of the tab "ID - Allocation Area" of the PCT14. > **Warning:** While the connection between FAM14 and PCT14 is active via USB, wireless telegrams cannot be sent. > **Note:** For Eltako devices, the switch actor must be taught in in directional button mode. The dim actor must be taught in in the mode P,L,C (also PCT). This is realized by the especially available instance and the Teach In button. (since IP-Symcon 2.5) > **Note:** The device Eltako FSB14 can only be taught in in RV 180/200 (Motor 1/2). | ID | Description | | --------- | ----------------------------------------------------- | | Device ID | Provided by the user. 0-127 in whole numbers possible | | Report ID | Sent by the device. Used for device allocation | #### Actor (OPUS) 1. The OPUS Config Tool is required in a current version, so a generic "Gateway" can be added. 2. In the gateway, the EURID of the used EnOcean gateway needs to be entered. (It is found below the EnOcean Gateway Splitter instance) [For older TCM310 it is eventually required to enter the BaseID] 3. "Connect" device in gateway [It is highlighted in blue then] and let the device program 3. Add devices manually via "Add Instance" in IP-Symcon and enter the known Device ID in the instance 4. Switching and receiving should be possible effortlessly ![OPUS Link](https://www.symcon.de/media/pages/service/dokumentation/modulreferenz/geraete/enocean/e8435ddebf-1790424938/enocean-opuslink.png) | ID | Description | | --------- | --------------------------------------------- | | Device ID | 8 digit EnOcean ID. It is found on the device | #### Actor (Actuator) - Enter Device ID and confirm with "Apply" - Click "Search" - Put device into teach in mode (see manufacturer manual) - Device confirms teach in (see manufacturer manual) - Select found ID, confirm with "OK" and "Apply" | ID | Description | | --------- | ----------------------------------------------------- | | Device ID | Provided by the user. 0-127 in whole numbers possible | | Report ID | Sent by the device. Used for device allocation | #### Sensor - Click "Search" - Wait for data receival (evntually press button) - Select found ID and confirm with "OK" The search dialog display a device only after it has received data. For a button, it can be pressed to call a sending process. For temperature sensors, waiting for the next interval or entering the ID manually is required. | ID | Description | | --------- | ---------------------------------------------- | | Device ID | Sent by the device. Used for device allocation | ### Tips & Tricks * To eliminate reception problems or to bridge large distances, maximum two repeater of type "TCM 120" can be used. * The manual for changing the Base ID (not to be confused with the Device ID) can be found [here (German)](https://www.symcon.de/assets/files/service/EnOceanBaseIDTool.pdf). Additional information about the used technology and sources of supply are available on online presence of EnOcean. Link: [https://www.enocean.com/en/](https://www.enocean.com/en/) ## ENO_DimSet Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-dimset/ `bool ENO_DimSet(int $InstanceID, int $Intensity)` **Parameters** - `$InstanceID` (int): ID of the device to be switched - `$Intensity` (int): 1..100 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 1..100 **Example** ```php ENO_DimSet(12345, 10); //Device dimmed to 10% ``` ## ENO_SetActiveMessage Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setactivemessage/ `bool ENO_SetActiveMessage(int $InstanceID, int $Message)` activates a certain message **Parameters** - `$InstanceID` (int): ID of the instance of the device to be switched - `$Message` (int): 0..8 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 0..8 **Example** ```php ENO_SetActiveMessage(12345, 2); ``` ## ENO_SetFanStage Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setfanstage/ `bool ENO_SetFanStage(int $InstanceID, int $FanStage)` sets the FanStage to a certain value **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$FanStage` (int): 0..4 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 0..4 **Example** ```php ENO_SetFanStage(12345, 4); //Device is set to automatic ``` ## ENO_SetIntensity Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setintensity/ `bool ENO_SetIntensity(int $InstanceID, bool $Status, int $Intensity)` **Parameters** - `$InstanceID` (int): ID of the device to be switched - `$Status` (bool): __TRUE__ for On, __FALSE__ for Off - `$Intensity` (int): 1..20, 1 = 5%, 20 = 100% **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 1..20, 1 = 5%, 20 = 100% **Example** ```php ENO_SetIntensity(12345, true, 10); //Device dimmed to about 50% ``` ## ENO_SetLockFanStage Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setlockfanstage/ `bool ENO_SetLockFanStage(int $InstanceID, bool $Locked)` **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Locked` (bool): __TRUE__ for on, __FALSE__ for off **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. __TRUE__ for on, __FALSE__ for off **Example** ```php ENO_SetLockFanStage(12345, true); ``` ## ENO_SetLockRoomOccupancy Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setlockroomoccupancy/ `bool ENO_SetLockRoomOccupancy(int $InstanceID, bool $Locked)` **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Locked` (bool): __TRUE__ for on, __FALSE__ for off **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. __TRUE__ for on, __FALSE__ for off **Example** ```php ENO_SetLockRoomOccupancy(12345, true); ``` ## ENO_SetMode Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setmode/ `bool ENO_SetMode(int $InstanceID, int $Value)` sets the actuator in a certain mode **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Value` (int): 0..5 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 0..5 **Example** ```php ENO_SetMode(12345, 1); //Actuator is set to summer mode ``` ## ENO_SetPosition Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setposition/ `bool ENO_SetPosition(int $InstanceID, int $Value)` **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Value` (int): 1..100 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 1..100 **Example** ```php ENO_SetPosition(12345, 10); ``` ## ENO_SetRoomOccupancy Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-setroomoccupancy/ `bool ENO_SetRoomOccupancy(int $InstanceID, bool $Occupied)` sets the occupancy to true/false **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Occupied` (bool): __TRUE__ for on, __FALSE__ for off **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. __TRUE__ for on, __FALSE__ for off **Example** ```php ENO_SetRoomOccupancy(12345, true); ``` ## ENO_SetTemperature Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-settemperature/ `bool ENO_SetTemperature(int $InstanceID, float $Value)` sets the actuator to a certain target temperature **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Value` (float): 1...100 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 1...100 **Example** ```php ENO_SetTemperature(12345, 22.7); ``` ## ENO_SetTemperature1 Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-settemperature1/ `bool ENO_SetTemperature1(int $InstanceID, float $Temperature)` sets the device to a certain temperature **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Temperature` (float): 1..100 **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 1..100 **Example** ```php ENO_SetTemperature1(12345, 10); ``` ## ENO_ShutterMoveDown Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-shuttermovedown/ `bool ENO_ShutterMoveDown(int $InstanceID)` moves the roller shutter down to the end position/stop **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. ID of the Instance of the device to be switched **Example** ```php ENO_ShutterMoveDown(12345); ``` ## ENO_ShutterMoveDownEx Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-shuttermovedownex/ `bool ENO_ShutterMoveDownEx(int $InstanceID, float $Runtime)` _Requires Symcon >= 4.2_ moves the roller shutter for a certain time **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Runtime` (float): How long the roller shutter should run for in seconds. (0 - 6535.5) **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. How long the roller shutter should run for in seconds. (0 - 6535.5) **Example** ```php //Move the roller shutter down for 10.5 seconds ENO_ShutterMoveDownEx(12345, 10.5); ``` ## ENO_ShutterMoveUp Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-shuttermoveup/ `bool ENO_ShutterMoveUp(int $InstanceID)` moves the roller shutter up to the end position/stop **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. ID of the Instance of the device to be switched **Example** ```php ENO_ShutterMoveUp(12345); ``` ## ENO_ShutterMoveUpEx Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-shuttermoveupex/ `bool ENO_ShutterMoveUpEx(int $InstanceID, float $Runtime)` _Requires Symcon >= 4.2_ moves the roller shutter for a certain time **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched - `$Runtime` (float): How long the roller shutter should run for in seconds. **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. How long the roller shutter should run for in seconds. **Example** ```php //Move the roller shutter up for 10.5 seconds ENO_ShutterMoveUpEx(12345, 10.5); ``` ## ENO_ShutterStop Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-shutterstop/ `bool ENO_ShutterStop(int $InstanceID)` stops a motion **Parameters** - `$InstanceID` (int): ID of the Instance of the device to be switched **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. ID of the Instance of the device to be switched **Example** ```php ENO_ShutterStop(12345); ``` ## ENO_SwitchMode Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-switchmode/ `bool ENO_SwitchMode(int $InstanceID, bool $Status)` **Parameters** - `$InstanceID` (int): ID of the device to be switched - `$Status` (bool): __TRUE__ for On, __FALSE__ for Off **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. __TRUE__ for On, __FALSE__ for Off **Example** ```php ENO_SwitchMode(12345, true); //Turn on device ``` ## ENO_SwitchModeEx Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/eno-switchmodeex/ `bool ENO_SwitchModeEx(int $InstanceID, bool $Status, int $SendMode)` **Parameters** - `$InstanceID` (int): ID of the device to be switched - `$Status` (bool): __TRUE__ for On, __FALSE__ for Off - `$SendMode` (int): 0 = NMessage, 1 = UMessage, 2 = Both (Like [ENO_SwitchMode](enocean.md)) **Returns** (bool): If the command succeeds, it returns __TRUE__, otherwise __FALSE__. 0 = NMessage, 1 = UMessage, 2 = Both (Like [ENO_SwitchMode](enocean.md)) **Example** ```php ENO_SwitchModeEx(12345, true, 0); //Send NMessage IPS_Sleep(500); //Warten ENO_SwitchModeEx(12345, true, 1); //Send UMessage ``` ## Device list Source: https://www.symcon.de/en/service/documentation/module-reference/devices/enocean/device-list/ #### Supported Gateways | Product | Description | | ----------------------------------------------------------------------------------------------------------------------------------- | -------------------------------------------------------------------------------------- | | EnOcean LAN Gateway (TCM310/TCM515 LAN Gateway)
[Product information](https://www.symcon.de/assets/files/product/enocean-lan-gateway.pdf) | IP Gateway | | BSC-BOR | USB Gateway | | EnOcean USB300 | USB Gateway | | EnOcean Pi | Raspberry Pi plug-in board | | EnOcean FGW14 (with FAM14) | USB/serial Gateway (operating mode 6) and
Radio extension FAM14 (operating mode 2) | | FAM USB | USB Gateway (must be entered as TCM 130) | | TCM130 | All devices that support the ESP2 protocol | | TCM310 | All devices that support the ESP3 protocol (Dolphin) | | TCM515 | All devices that support the ESP3 protocol (Dolphin) | | Thermokon STC-Ethernet | IP Gateway | #### Supported Devices The following devices have been examined for their compatibility with IP-Symcon. On [request](https://www.symcon.de/en/contact-us/) we will be happy to check other devices that are not listed. ##### General | Product | Description | | ------- | ------------------------------ | | PTM 200 | Button/Expert | | PTM 200 | Switch | | RCM 1xx | Switching actuator (universal) | | STM100 | Sensor | | STM250 | Sensor | ##### alphaEOS | Product | Description | | ---------- | ------------------------------------------------ | | Drive B2 | Radio actuator | | SENSE TF-H | Indoor climate sensor (temperature and humidity) | ##### Eltako | Product | Description | EEP number (See EEP list below) | | -------------- | --------------------------------------------------------------------------- | -------------------------------------------------- | | DSZ14DRS | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | DSZ14WDRS | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | F2L14 | RS485 bus actuator 2-stage ventilation relay | stand-alone module | | F3Z14D | RS485 bus electricity meter collector | EEP: A5-12-01 | | F4HK14 | 4-channel heating-cooling relay | stand-alone module | | F4T65 | Wireless sensors without batteries or wires | EEP: F6-02-01 | | FABH65S | Outdoor motion/brightness sensor | stand-alone module | | FADS60-230V | Wireless actuator for outdoor twilight sensor | stand-alone module | | FAE14LPR | Individual room control heating/cooling for 2 zones | stand-alone module | | FAE14SSR | Individual room control heating/cooling for 2 zones with solid-state relays | stand-alone module | | FAFT60 | Outdoor humidity temperature sensor | stand-alone module | | FAH60 | Outdoor brightness sensor | stand-alone module | | FAH60B | Outdoor brightness sensor | stand-alone module,
EEP: A5-06-01 | | FAH63 | Outdoor brightness sensor | stand-alone module | | FAH65S | Outdoor brightness sensor | stand-alone module | | FASM60 | Wireless outdoor transmitter module | EEP: F6-02-01 | | FBH65B | Motion/brightness sensor | stand-alone module | | FBH65S | Motion/brightness sensor | stand-alone module | | FBH65TFB | Motion/brightness sensor | stand-alone module | | FCO2TF65 | CO2 sensor | EEP: A5-09-04 | | FD62NP-230V | Wireless universal dimming actuator without N-connection | stand-alone module | | FD62NPN-230V | Wireless universal dimming actuator | stand-alone module | | FFR14 | RS485 bus actuator field release switch | stand-alone module | | FFR61-230V | Field release switch | stand-alone module | | FHF | Wireless sensor window handle | EEP: F6-10-00 | | FHK14 | Wireless actuator for heating/cooling relays | stand-alone module | | FHK61SSR-230V | Wireless actuator for heating/cooling relays | stand-alone module | | FHK61U-230V | Wireless actuator for heating relay | stand-alone module | | FIFT65S | Indoor humidity temperature sensor | stand-alone module | | FIH65S | Outdoor brightness sensor | stand-alone module | | FIH65Bv | Indoor brightness sensor | EEP: A5-06-02 | | FIUS65 | Indoor wireless flush-mounted signal generator | stand-alone module | | FJ62/12-36V DC | Wireless blind and roller shutter actuator | stand-alone module | | FJ62NP-230V | Wireless blind and roller shutter actuator | stand-alone module | | FKC | Wireless card switch | stand-alone module | | FKF | Wireless card switch | stand-alone module | | FL62-230V | Wireless light actuator 10A/250V AC | stand-alone module | | FL62NP-230V | Wireless light actuator 10A/250V AC | stand-alone module | | FLC61-230V | Wireless light controller | stand-alone module | | FMS14 | RS485 bus actuator multifunction impulse switching relay | stand-alone module | | FMS61NP-230V | Wireless actuator multifunction impulse switch | stand-alone module | | FMZ14 | RS485 bus actuator multifunction time relay | stand-alone module | | FMZ61-230V | Wireless actuator multifunction time relay | stand-alone module | | FR62-230V | Wireless relay actuator 10 A/250 V AC | stand-alone module | | FR62NP-230V | Wireless relay actuator 10 A/250 V AC | stand-alone module | | FRGBW71L | Dimming actuator | stand-alone module | | FRW | Wireless sensor smoke alarm device | stand-alone module | | FSB14 | Actuator for shading elements and roller shutters | stand-alone module | | FSB61 | Wireless actuator for shading elements and roller shutters | stand-alone module | | FSB71 | Wireless actuator for shading elements and roller shutters | stand-alone module | | FSDG14 | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FSG14/1-10V | Dimming actuator | stand-alone module | | FSG71/1-10V | Dimming actuator | stand-alone module | | FSM14 | Radio transmitter module | EEP: F6-02-01 | | FSM60B | 4-channel input | EEP: A5-30-03 | | FSM61 | Wireless 2-way transmitter module | EEP: F6-01-01 | | FSR14SSR | RS485 bus actuator 2-channel impulse switching relay noiseless | stand-alone module | | FSR14-2x | RS485 bus actuator 2-channel impulse switching relay | stand-alone module | | FSR14-4x | RS485 bus actuator 4-channel impulse switching relay | stand-alone module | | FSR61-230V | Wireless actuator for impulse switching relays | stand-alone module | | FSR61/8-24V | Wireless actuator for impulse switching relays | stand-alone module | | FSR61LN-230V | Wireless actuator for impulse switching relays | stand-alone module | | FSR61NP-230V | Wireless actuator for impulse switching relays | stand-alone module | | FSR61VA | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FSR61VA-10A | Wireless actuator for 10A impulse switching relays | stand-alone module | | FSR71 | Wireless actuator for 2-channel impulse switching relays | stand-alone module | | FSS12 | Wireless electricity meter transmitter module | EEP: A5-12-01 | | FSSA-230V | Wireless actuator socket switch actuator | stand-alone module | | FSU14 | RS485 bus display timer | EEP: A5-13-04 | | FSU65D | Wireless sensor timer with display | EEP: F6-01-01 | | FSUD-230V | Dimming actuator | stand-alone module | | FSVA-230V | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FT-FTSB | Tip wireless humidity/temperature sensor | EEP: A5-04-02 | | FT4F | Wireless sensor surface wireless pushbutton | EEP: F6-02-01 | | FT55 | Wireless sensor surface wireless pushbutton | EEP: F6-02-01 | | FTF65S | Temperature sensor | EEP: A5-02-05 | | FTK | Wireless window/door contact | EEP: D5-00-01 | | FTKB | Wireless window/door contact | EEP: D5-00-01 | | FTKE | Wireless window/door contact | EEP: F6-10-00 | | FTN14 | RS485 bus actuator staircase lighting overrun switch | stand-alone module | | FTN61NP-230V | Wireless actuator for staircase lighting overrun switch | stand-alone module | | FTR65DS | Wireless sensor temperature controller | stand-alone module | | FTR65HS | Wireless sensor temperature controller | stand-alone module | | FTR78S | Wireless temperature controller with rotary knob | EEP: A5-10-03 | | FUD14 | Dimming actuator | stand-alone module | | FUD14-800W | Dimming actuator | stand-alone module | | FUD61NP | Dimming actuator | stand-alone module | | FUD61NPN | Dimming actuator | stand-alone module | | FUD70S-230V | Dimming actuator | stand-alone module | | FUD71 | Dimming actuator | stand-alone module | | FUTH55D | Wireless sensor clock thermo-hygrostat | stand-alone module | | FUTH65D | Wireless sensor clock thermo-hygrostat | stand-alone module | | FWS61 | Wireless weather data transmitter module | EEP: A5-13-01, A5-13-02 | | FWWKW71L | PWM Dimming actuator for LED | stand-alone module | | FWZ12 | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FWZ14 | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FWZ61 | Wireless single-phase energy meter transmitter module | EEP: A5-12-01 | | FZK14 | RS485 bus actuator time relay for card switches/smoke alarm devices | stand-alone module | | FZK61NP-230V | Wireless actuator for time relays with card switch/smoke alarm device | stand-alone module | | FZS | Wireless sensor pull switch | stand-alone module | | FMMS44SB | Wireless mini multisensor | EEP: D2-14-41 | ##### Hoppe | Product | Description | EEP number (See EEP list below) | | ----------- | --------------------------------------------- | -------------------------------------------------- | | FHF | Window handle | F6-10-00 | | SecuSignal | eWindow handle Amsterdam E0400/FR-408 F69 | F6-10-00 | | SecuSignal | eWindow handle Atlanta 0530S/FR-408 100 Nm F9 | F6-10-00 | | SecuSignal | eWindow handle Toulon E0400/FR-408 F69 | F6-10-00 | | ConnectHome | eWindow handle Tokyo | F6-10-00 | | ConnectHome | eWindow handle New York | F6-10-00 | ##### HORA | Product | Description | | ------------- | ----------- | | SmartDrive MX | Actuator | ##### Kieback & Peter | Product | Description | | ------- | -------------- | | MD15 | Small actuator | ##### Maco | Product | Description | EEP number (See EEP list below) | | -------------------------- | ------------------ | -------------------------------------------------- | | Smart Ready Sensor eTRONIC | Door/window sensor | EEP: A5-14-01 | ##### NodOn | Product | Description | EEP number (See EEP list below) | | ----------- | ---------------------------------------------- | -------------------------------------------------- | | ASP-2-1-00 | Smart Plug | EEP: D2-01-0A | | ASP-2-1-01 | Smart Plug Metering | EEP: D2-01-0B | | ASP-2-1-10 | Smart Plug | EEP: D2-01-0A | | ASP-2-1-11 | Smart Plug Metering | EEP: D2-01-0B | | SIN-2-1-01 | In-wall Multifunction Relay Switch 1-Channel | EEP: D2-01-0F | | SIN-2-2-01 | In-wall ON/OFF Lighting Relay Switch 2-Channel | EEP: D2-01-0B | | SIN-2-RS-01 | Roller Shutter Relay Switch | EEP: D2-05-00 | ##### OPUS | Product | Description | EEP number (See EEP list below) | | ------------ | --------------------------------------------------------------- | -------------------------------------------------- | | 514.441 | 55 Wall transmitter module standard | EEP: F6-02-01 | | 561.150.9052 | Temperature sensor (2 buttons) | EEP: A5-10-12 | | 561.150.9069 | Temperature sensor (4 buttons) | EEP: A5-10-22 | | 563.010-C* | Bridge 1 channel | EEP: D2-01-01 | | 563.014-C* | Bridge 1 channel, 16A | EEP: D2-01-01 | | 563.020-C* | Bridge 2 channel | EEP: D2-01-11 | | 563.031-C* | Bridge roller shutter/ blind | EEP: D2-05-02 | | 563.035-C* | Bridge dimmer | EEP: D2-01-03 | | 563.051-C | Smart Motion Sensor (light) | EEP: F6-02-01 | | 563.052-C | Smart motion sensor multifunction | EEP: F6-02-01 | | 563.053 | Smart Motion Sensor Ambient Assisted Living - Inability to move | EEP: A5-07-03 | | 563.055-C | Smart Motion Sensor (presence) | EEP: A5-07-03 | | 563.067-C | Water alarm (instant alarm) | EEP: F6-05-01 | | 563.068-C | Water alarms (source disks) | EEP: A5-30-03 | | 563.069-C | Smoke alarm device | EEP: F6-05-02 | *Requires setup via Opus Config Tool (563.040) ##### PEHA | Product | Description | | ------- | ----------------------------------------------- | | Various | All devices that support EEP | ##### Thermokon | Product | Description | | ------- | -------------------- | | SR04 | Temperature/humidity | | SAB02 | Actuator | | Thanos | Room control unit | ### EEP All devices that use the following EEPs are supported by IP-Symcon. ##### Actuators | New | since version | Old | Description | | -------- | ------------- | -------- | ---------------------------- | | A5-20-12 | 4.0 | 07-20-12 | Temperature Controller Input | ##### Bi-Directional | New | since version | Old | Description | | -------- | ------------- | -------- | ----------------------------------------------------------------------------------- | | A5-20-01 | 4.0 | 07-20-01 | Battery Powered Actuator | | D2-01-00 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-01 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-02 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-03 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-04 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-05 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-06 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-07 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-08 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-09 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0A | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0B | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0C | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0D | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0E | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-0F | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-10 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-11 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-12 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-13 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-01-14 | 4.3 | | Electronic switches and dimmer with Energy Measurement and Local Content | | D2-03-00 | 5.5 | | Light, Switching + Blind Control Type 0x00 | | D2-03-0A | 5.5 | | Push Button – Single Button | | D2-03-10 | 5.5 | | Mechanical Handle | | D2-05-00 | 5.3 | | Blinds Control for Position/Angle Type 0x00 | | D2-05-01 | 5.3 | | Blinds Control for Position/Angle Type 0x01 | | D2-05-02 | 5.3 | | Blinds Control for Position/Angle Type 0x02 | | D2-06-01 | 4.3 | | Multisensor Window Handle - Alarm, Position Sensor, Vacation Mode, Optional Sensors | | D2-07-00 | 5.5 | | Locking Systems Control - Mortise lock | | D2-11-01 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x01 | | D2-11-02 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x02 | | D2-11-03 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x03 | | D2-11-04 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x04 | | D2-11-05 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x05 | | D2-11-06 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x06 | | D2-11-07 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x07 | | D2-11-08 | 5.3 | | Room Operating Panel (BI-DIR) Type 0x08 | | D2-15-00 | 5.5 | | People Activity Counter | | D2-A0-01 | 5.5 | | Valve Control (BI-DIR) | ##### Sensors | New | since version | Old | Description | | -------- | ------------- | -------- | --------------------------------------------------------------------------------------- | | A5-02-01 | 4.0 | 07-02-01 | Temperature Sensor Range -40°C to 0°C | | A5-02-02 | 4.0 | 07-02-02 | Temperature Sensor Range -30°C to +10°C | | A5-02-03 | 4.0 | 07-02-03 | Temperature Sensor Range -20°C to +20°C | | A5-02-04 | 4.0 | 07-02-04 | Temperature Sensor Range -10°C to +30°C | | A5-02-05 | 4.0 | 07-02-05 | Temperature Sensor Range 0°C to +40°C | | A5-02-06 | 4.0 | 07-02-06 | Temperature Sensor Range +10°C to +50°C | | A5-02-07 | 4.0 | 07-02-07 | Temperature Sensor Range +20°C to +60°C | | A5-02-08 | 4.0 | 07-02-08 | Temperature Sensor Range +30°C to +70°C | | A5-02-09 | 4.0 | 07-02-09 | Temperature Sensor Range +40°C to +80°C | | A5-02-0A | 4.0 | 07-02-0A | Temperature Sensor Range +50°C to +90°C | | A5-02-0B | 4.0 | 07-02-0B | Temperature Sensor Range +60°C to +100°C | | A5-02-10 | 4.0 | 07-02-10 | Temperature Sensor Range -60°C to +20°C | | A5-02-11 | 4.0 | 07-02-11 | Temperature Sensor Range -50°C to +30°C | | A5-02-12 | 4.0 | 07-02-12 | Temperature Sensor Range -40°C to +40°C | | A5-02-13 | 4.0 | 07-02-13 | Temperature Sensor Range -30°C to +50°C | | A5-02-14 | 4.0 | 07-02-14 | Temperature Sensor Range -20°C to +60°C | | A5-02-15 | 4.0 | 07-02-15 | Temperature Sensor Range -10°C to +70°C | | A5-02-16 | 4.0 | 07-02-16 | Temperature Sensor Range 0°C to +80°C | | A5-02-17 | 4.0 | 07-02-17 | Temperature Sensor Range +10°C to +90°C | | A5-02-18 | 4.0 | 07-02-18 | Temperature Sensor Range +20°C to +100°C | | A5-02-19 | 4.0 | 07-02-19 | Temperature Sensor Range +30°C to +110°C | | A5-02-1A | 4.0 | 07-02-1A | Temperature Sensor Range +40°C to +120°C | | A5-02-1B | 4.0 | 07-02-1B | Temperature Sensor Range +50°C to +130°C | | A5-02-20 | 4.0 | 07-02-20 | 10 Bit Temperature Sensor Range -10°C to +41.2°C | | A5-02-30 | 4.0 | 07-02-30 | 10 Bit Temperature Sensor Range -40°C to +62.3°C | | A5-04-01 | 4.0 | 07-04-01 | Range 0°C to +40°C and 0% to 100% | | A5-04-02 | 4.1 | 07-04-02 | Range -20°C to +60°C and 0% to 100% | | A5-04-03 | 4.1 | 07-04-03 | Range -20°C to +60°C 10bit-measurement and 0% to 100% | | A5-04-03 | 5.3 | 07-04-03 | Temperature and Humidity Sensor | | A5-06-01 | 4.0 | 07-06-01 | Range 300lx to 60.000lx | | A5-06-02 | 4.0 | 07-06-02 | Range 0lx to 1.020lx | | A5-06-03 | 4.0 | 07-06-03 | 10-bit measurement (1-Lux resolution) with range 0lx to 1000lx | | A5-07-01 | 4.0 | 07-07-01 | Occupancy with Supply voltage monitor | | A5-07-01 | 5.3 | 07-07-01 | gN-Deckenbewegungsmelder 360° | | A5-07-01 | 5.3 | 07-07-01 | Desk Occupancy | | A5-07-02 | 4.0 | 07-07-02 | Occupancy with Supply voltage monitor | | A5-07-03 | 4.0 | 07-07-03 | Occupancy with Supply voltage monitor and 10-bit illumination measurement | | A5-08-01 | 4.0 | 07-08-01 | Range 0lx to 510lx | | A5-08-01 | 4.0 | 07-08-01 | 0°C to +51°C and Occupancy Button | | A5-08-02 | 4.0 | 07-08-02 | Range 0lx to 1020lx | | A5-08-02 | 4.0 | 07-08-02 | 0°C to +51°C and Occupancy Button | | A5-08-03 | 4.0 | 07-08-03 | Range 0lx to 1530lx | | A5-08-03 | 4.0 | 07-08-03 | -30°C to +50°C and Occupancy Button | | A5-09-01 | 4.0 | 07-09-01 | CO Sensor (not in use) | | A5-09-02 | 4.0 | 07-09-02 | CO-Sensor 0 ppm to 1020 ppm | | A5-09-04 | 4.0 | 07-09-04 | CO2 Sensor | | A5-09-04 | 5.3 | 07-09-04 | CO2, Temperature and Humidity Sensor | | A5-09-05 | 4.0 | 07-09-05 | VOC Sensor | | A5-09-06 | 4.0 | 07-09-06 | Radon | | A5-09-07 | 4.0 | 07-09-07 | Particles | | A5-09-08 | 4.0 | 07-09-08 | Pure CO2 Sensor | | A5-10-01 | 4.0 | 07-10-01 | Temperature Sensor | | A5-10-01 | 4.0 | 07-10-01 | Set Point | | A5-10-01 | 4.0 | 07-10-01 | Fan Speed and Occupancy Control | | A5-10-02 | 4.0 | 07-10-02 | Temperature Sensor | | A5-10-02 | 4.0 | 07-10-02 | Set Point | | A5-10-02 | 4.0 | 07-10-02 | Fan Speed and Day/Night Control | | A5-10-03 | 4.0 | 07-10-03 | Temperature Sensor | | A5-10-03 | 4.0 | 07-10-03 | Set Point Control | | A5-10-04 | 4.0 | 07-10-04 | Temperature Sensor | | A5-10-04 | 4.0 | 07-10-04 | Set Point and Fan Speed Control | | A5-10-05 | 4.0 | 07-10-05 | Temperature Sensor | | A5-10-05 | 4.0 | 07-10-05 | Set Point and Occupancy Control | | A5-10-06 | 4.0 | 07-10-06 | Temperature Sensor | | A5-10-06 | 4.0 | 07-10-06 | Set Point and Day/Night Control | | A5-10-07 | 4.0 | 07-10-07 | Temperature Sensor | | A5-10-07 | 4.0 | 07-10-07 | Fan Speed Control | | A5-10-08 | 4.0 | 07-10-08 | Temperature Sensor | | A5-10-08 | 4.0 | 07-10-08 | Fan Speed and Occupancy Control | | A5-10-09 | 4.0 | 07-10-09 | Temperature Sensor | | A5-10-09 | 4.0 | 07-10-09 | Fan Speed and Day/Night Control | | A5-10-0A | 4.0 | 07-10-0A | Temperature Sensor | | A5-10-0A | 4.0 | 07-10-0A | Set Point Adjust and Single Input Contact | | A5-10-0B | 4.0 | 07-10-0B | Temperature Sensor and Single Input Contact | | A5-10-0C | 4.0 | 07-10-0C | Temperature Sensor and Occupancy Control | | A5-10-0D | 4.0 | 07-10-0D | Temperature Sensor and Day/Night Control | | A5-10-10 | 4.0 | 07-10-10 | Temperature and Humidity Sensor | | A5-10-10 | 4.0 | 07-10-10 | Set Point and Occupancy Control | | A5-10-11 | 4.0 | 07-10-11 | Temperature and Humidity Sensor | | A5-10-11 | 4.0 | 07-10-11 | Set Point and Day/Night Control | | A5-10-12 | 4.0 | 07-10-12 | Temperature and Humidity Sensor and Set Point | | A5-10-13 | 4.0 | 07-10-13 | Temperature and Humidity Sensor | | A5-10-13 | 4.0 | 07-10-13 | Occupancy Control | | A5-10-14 | 4.0 | 07-10-14 | Temperature and Humidity Sensor | | A5-10-14 | 4.0 | 07-10-14 | Day/Night Control | | A5-10-15 | 4.0 | 07-10-15 | 10 Bit Temperature Sensor | | A5-10-15 | 4.0 | 07-10-15 | 6 bit Set Point Control | | A5-10-16 | 4.0 | 07-10-16 | 10 Bit Temperature Sensor | | A5-10-16 | 4.0 | 07-10-16 | 6 bit Set Point Control;Occupancy Control | | A5-10-17 | 4.0 | 07-10-17 | 10 Bit Temperature Sensor | | A5-10-17 | 4.0 | 07-10-17 | Occupancy Control | | A5-10-18 | 4.0 | 07-10-18 | Illumination | | A5-10-18 | 4.0 | 07-10-18 | Temperature Set Point | | A5-10-18 | 4.0 | 07-10-18 | Temperature Sensor | | A5-10-18 | 4.0 | 07-10-18 | Fan Speed and Occupancy Control | | A5-10-19 | 4.0 | 07-10-19 | Humidity | | A5-10-19 | 4.0 | 07-10-19 | Temperature Set Point | | A5-10-19 | 4.0 | 07-10-19 | Temperature Sensor | | A5-10-19 | 4.0 | 07-10-19 | Fan Speed and Occupancy Control | | A5-10-1A | 4.0 | 07-10-1A | Supply voltage monitor | | A5-10-1A | 4.0 | 07-10-1A | Temperature Set Point | | A5-10-1A | 4.0 | 07-10-1A | Temperature Sensor | | A5-10-1A | 4.0 | 07-10-1A | Fan Speed and Occupancy Control | | A5-10-1B | 4.0 | 07-10-1B | Supply Voltage Monitor | | A5-10-1B | 4.0 | 07-10-1B | Illumination | | A5-10-1B | 4.0 | 07-10-1B | Temperature Sensor | | A5-10-1B | 4.0 | 07-10-1B | Fan Speed and Occupancy Control | | A5-10-1C | 4.0 | 07-10-1C | Illumination | | A5-10-1C | 4.0 | 07-10-1C | Illumination Set Point | | A5-10-1C | 4.0 | 07-10-1C | Temperature Sensor | | A5-10-1C | 4.0 | 07-10-1C | Fan Speed and Occupancy Control | | A5-10-1D | 4.0 | 07-10-1D | Humidity | | A5-10-1D | 4.0 | 07-10-1D | Humidity Set Point | | A5-10-1D | 4.0 | 07-10-1D | Temperature Sensor | | A5-10-1D | 4.0 | 07-10-1D | Fan Speed and Occupancy Control | | A5-10-1E | 5.5 | 07-10-1E | Temperature Sensor, Supply Voltage, Light, Fan Speed, and Occupancy Control | | A5-10-1F | 4.0 | 07-10-1F | Temperature Sensor | | A5-10-1F | 4.0 | 07-10-1F | Set Point | | A5-10-1F | 4.0 | 07-10-1F | Fan Speed | | A5-10-1F | 4.0 | 07-10-1F | Occupancy and Unoccupancy Control | | A5-10-20 | 4.0 | 07-10-20 | Temperature and Set Point with Special Heating States | | A5-10-21 | 4.0 | 07-10-21 | Temperature | | A5-10-21 | 4.0 | 07-10-21 | Humidity and Set Point with Special Heating States | | A5-10-22 | 5.5 | 07-10-22 | Temperature Sensor, Set Point, Humidity, and Fan Speed | | A5-10-23 | 5.5 | 07-10-23 | Temperature Sensor, Set Point, Humidity, Fan Speed, and Occupancy Control | | A5-11-01 | 4.0 | 07-11-01 | Lighting Controller | | A5-11-02 | 4.0 | 07-11-02 | Temperature Controller Output | | A5-11-03 | 4.0 | 07-11-03 | Blind Status | | A5-11-04 | 4.0 | 07-11-04 | Extended Lighting Status | | A5-12-00 | 4.0 | 07-12-00 | Counter | | A5-12-00 | 5.3 | 07-12-00 | Operations Counting | | A5-12-01 | 4.0 | 07-12-01 | Electricity | | A5-12-02 | 4.0 | 07-12-02 | Gas | | A5-12-03 | 4.0 | 07-12-03 | Water | | A5-13-01 | 4.0 | 07-13-01 | Weather Station | | A5-13-02 | 4.0 | 07-13-02 | Sun Intensity | | A5-13-03 | 4.0 | 07-13-03 | Date Exchange | | A5-13-04 | 4.0 | 07-13-04 | Time and Day Exchange | | A5-13-05 | 4.0 | 07-13-05 | Direction Exchange | | A5-14-01 | 4.0 | 07-14-01 | Single Input Contact (Window/Door) | | A5-14-01 | 4.0 | 07-14-01 | Supply voltage monitor | | A5-14-02 | 4.0 | 07-14-02 | Single Input Contact (Window/Door) | | A5-14-02 | 4.0 | 07-14-02 | Supply voltage monitor and Illumination | | A5-14-03 | 4.0 | 07-14-03 | Single Input Contact (Window/Door) | | A5-14-03 | 4.0 | 07-14-03 | Supply voltage monitor and Vibration | | A5-14-04 | 4.0 | 07-14-04 | Single Input Contact (Window/Door) | | A5-14-04 | 4.0 | 07-14-04 | Supply voltage monitor | | A5-14-04 | 4.0 | 07-14-04 | Vibration and Illumination | | A5-14-05 | 4.0 | 07-14-05 | Vibration/Tilt | | A5-14-05 | 4.0 | 07-14-05 | Supply voltage monitor | | A5-14-05 | 5.3 | 07-14-05 | Chair Occupancy Solar Sensor | | A5-14-06 | 4.0 | 07-14-06 | Vibration/Tilt | | A5-14-06 | 4.0 | 07-14-06 | Illumination and Supply voltage monitor | | A5-14-07 | 5.0 | 07-14-07 | Dual door contact with States (Open/Closed/Locked/Unlocked) | | A5-14-07 | 5.0 | 07-14-07 | Supply voltage monitor | | A5-14-08 | 5.0 | 07-14-08 | Dual door contact with States (Open/Closed/Locked/Unlocked) | | A5-14-08 | 5.0 | 07-14-08 | Supply voltage monitor and Vibration detection | | A5-14-09 | 5.0 | 07-14-09 | Window/Door Sensor with States (Open/Closed/Tilt) | | A5-14-09 | 5.0 | 07-14-09 | Supply voltage monitor | | A5-14-0A | 5.0 | 07-14-0A | Window/Door Sensor with States (Open/Closed/Tilt) | | A5-14-0A | 5.0 | 07-14-0A | Supply voltage monitor and Vibration detection | | A5-20-01 | 5.3 | 07-14-01 | Heating Valve Controller | | A5-20-06 | 5.5 | 07-20-06 | Heating Valve Controller | | A5-30-01 | 4.0 | 07-30-01 | Single Input Contact | | A5-30-01 | 4.0 | 07-30-01 | Battery Monitor | | A5-30-02 | 4.0 | 07-30-02 | Single Input Contact | | A5-30-03 | 4.0 | 07-30-03 | 4 Digital Inputs | | A5-30-03 | 4.0 | 07-30-03 | Wake and Temperature | | A5-30-04 | 4.0 | 07-30-04 | 3 Digital Inputs | | A5-30-04 | 4.0 | 07-30-04 | 1 Digital Input 8 Bits | | A5-37-01 | 4.0 | 07-37-01 | Demand Response | | A5-38-08 | 4.0 | 07-38-08 | Gateway | | A5-38-09 | 4.0 | 07-38-09 | Extended Lighting-Control | | D2-14-30 | 6.0 | | Sensor for Smoke, Air quality, Hygrothermal comfort, Temperature and Humidity | | D2-14-41 | 6.4 | | Sensor for Humidity, Illumination, Temperature, Dissolved oxegen, Contact, Acceleration | | D2-15-00 | 5.4 | | People Activity Counter | | D2-32-00 | 4.3 | | A.C. Current Clamp | | D2-32-00 | 5.3 | | Single Channel CT Clamp | | D2-32-01 | 4.3 | | A.C. Current Clamp | | D2-32-02 | 4.3 | | A.C. Current Clamp | | D5-00-01 | 4.0 | 06-00-01 | Single Input Contact | | D5-00-01 | 5.3 | 06-00-01 | Magnet Contact | | F6-01-01 | 5.5 | 05-01-01 | Push Button | | F6-02-01 | 4.0 | 05-02-01 | Light and Blind Control - Application Style 1 | | F6-02-02 | 4.0 | 05-02-02 | Light and Blind Control - Application Style 2 | | F6-02-03 | 4.0 | 05-02-03 | Light Control - Application Style 1 | | F6-02-04 | 4.0 | 05-02-04 | Light and blind control ERP2 | | F6-03-01 | 4.0 | 05-03-01 | Light and Blind Control - Application Style 1 | | F6-03-02 | 4.0 | 05-03-02 | Light and Blind Control - Application Style 2 | | F6-04-01 | 4.0 | 05-04-01 | Key Card Activated Switch | | F6-04-02 | 4.0 | 05-04-02 | Key Card Activated Switch ERP2 | | F6-05-00 | 5.0 | 05-05-00 | Wind Speed Threshold Detector | | F6-05-01 | 4.0 | 05-05-01 | Liquid Leakage Sensor (mechanic harvester) | | F6-05-02 | 5.0 | 05-05-02 | Smoke Detector | | F6-10-00 | 4.1 | 05-10-00 | Window Contact Sensor | | F6-10-01 | 5.5 | 05-10-01 | Window Handle ERP2 |