NRG-Stack SteuerboxHub
Author: DG65
Receives the grid operator's power limit under § 14a EnWG (the German rule on controllable consumption devices), via control box contacts or EEBUS, and provides it to an energy management system.
Description: The package contains two modules. "NRG-Stack SteuerboxHub" captures the control signal through potential-free contacts (ripple control receiver, FNN three-step scheme, with a calculator for the simultaneity factor) and reports through SBH_GetState whether and how strongly consumption is currently limited, with a timestamp. "NRG-Stack SteuerboxHub EEBUS" is a full control hub attached directly to the NRG-Stack EEBUS Gateway (use cases LPC and LPP, time-limited limits, failsafe limits after 120 s without a heartbeat) and provides the same information through SBHE_GetState. Neither module controls anything itself. An energy management system or your own script has to enforce the limit. The form and messages are available in German and English.
Included Modules
- NRG-Stack SteuerboxHub
- NRG-Stack SteuerboxHub EEBUS
Version History
- New: the EEBUS path is its own module "NRG-Stack SteuerboxHub EEBUS". It attaches directly to the EEBUS gateway and communicates through the data flow instead of public functions. Its contract is SBHE_GetState (same fields as SBH_GetState).
- New: both modules share a common base class for the form and the calculator.
- Change: "NRG-Stack SteuerboxHub" is now for contacts only. A former instance set to EEBUS shows a note and delivers no signal.
- Update from 0.5.0: re-enter the rated values and switch the energy management system to SBHE_GetState.