Heating Control (legacy)
This is a deprecated version. From version 5.0 onwards it is recommended to use the new Heating Control version.
Description
The heating module (legacy) is a two-point controller for regulating temperatures in living spaces. It compares the target value with the actual value and switches the configured transmit instances on or off directly. Alternatively, a handler script can be executed which takes care of switching.
Settings
| Setting | Description |
|---|---|
| Source Variable | Variable that contains the actual value. |
| Hysteresis | Temperature difference between the switch-on and switch-off point; Example: T-Target = 20.0 degrees and hysteresis = 0.4; The actuator is switched on when dropping below 19.8 degrees and switched off when exceeding 20.2 degrees. |
| SetBack | Temperature in °C by which the target is lowered if one or more of the "SetBack Variables" are TRUE. |
| Transmit Devices | Instances that are switched. For thermal actuators that are open when de-energized, "Invert" must be activated. The supported instances are listed below. |
| Override Variables | Can be e.g. status variables of window contacts. When TRUE, the output of the controller remains off. |
| SetBack Variables | Can be e.g. presence variables of motion or presence detectors. If no person is in a room, energy can be saved by lowering the temperature. |
| Resend Interval | Interval in minutes in which the current state is sent again, in case a (radio) command was not processed correctly. With 0 nothing is resent. |
| Handler Script | Expert setting: If a script is selected, the transmit instances are not switched directly. Instead, the script is executed on each switching operation. The necessary data is available in the System Variables. |
| Test Center | To check the function of the controller, a target temperature can be entered here. The actuator must then turn on or off as desired. |
Scripts executed by the Heating Control (legacy) include these System Variables
| Status variables | Ident | Description |
|---|---|---|
| Target Value | TargetValueVariable | Contains the target temperature. |
| Override | OverrideVariable | If TRUE, at least one override variable is also TRUE (OR operation) and the actuator remains off. |
| SetBack | SetBackVariable | If TRUE, the setback is active. |
| Heating | HeatingVariable | Reflects the output of the controller. Inverting the transmit instances has no effect on this variable. |
The target value can also be set via HC_TargetValue.
Supported transmit instances
Without a handler script, the following instances can be switched directly:
- ALLNET
- DMX
- EnOcean RCM100 and Opus
- FS20
- HomeMatic
- KNX EIS
- LCN (output and relay)
- ModBus
- Siemens
- xComfort switch and dimmer
- Z-Wave
If an instance cannot be switched, a warning is written to the message log.
Since the PC (controller) can fail at any time, a temperature limiter / safety shutdown must also be installed to prevent injury or damage.